Datos Técnicos

Technical characteristics

Power supply 100-240 V CA, 50/60 Hz, calibración automática o 24 V CC
Consumption 20 w
Operating temperature and
humidity limits
 -30 +54ºC

Systems

TES-01 EX TES-01 IP
Housing Gery coloured cast aluminium explosion proof, copper free Mild steel painted with aluminium front plate
Dimensions (l,w,h) 265x230x150 mm 300x200x155 mm
Mass 10 kg

5 kg

Conections 4 x M20 x 1,5 mm

3  x M20 cable glands, clamping range 5-10 mm

Bypass Optional via separate key switch Integrated
ATEX Information Approved for use in zones 1, 2, 21 and 22 Approved for use in zones 21 and 22

Accessories

Earth clamps

 

Earth clamp  CL 1 

Material: Aluminium
Size: 260 mm
Clamp jaw opening: 3 to 15 mm
Accessories : Male connector assembled
Use: Industrial environment, intensive use

ATEX relevant data:

  • Zones: Passive Ex accessories for Ex zones 0 or 20
  • Certificate: ISSeP 04ATEX084X
  • Markings: II 1GD Ex ia IIC; IIIC
Earth clamp CM 1 

Material: SS304
Size: 210 mm
Clamp jaw opening: 3 to 35 mm
Accessories : Male connector assembled
Use: Industrial environment, regular use

ATEX relevant data:

  • Zones: Passive Ex accessories for Ex zones 0 or 20
  • Certificate: ISSeP 04ATEX084X
  • Markings: II 1GD Ex ia IIC; IIIC
Earth clamp CS 1 

Material: SS 304
Size: 162 mm
Clamp jaw opening: 3 to 35 mm
Accessories : Male connector assembled
Use: Industrial environment, light use

ATEX relevant data:

  • Zones: Passive Ex accessories for Ex zones 0 or 20
  • Certificate: ISSeP 04ATEX084X
  • Markings: II 1GD Ex ia IIC; IIIC

 

Cables

Spiral cable SP 1/10 

Material: TPE-E with sheath in UV resistant and fire retardant plastic RAL 5015
Cable: 8 mm, 3 x 0,75 mm2
Length: Up to 10 m when not retracted; approx. 1 m when retracted
Accessories: F connector, assembled

Cable reel CR 1/65

Material: Aluminium housing
Cable: H05RN-F 2 X 1,5 + 1,5 mm2, connection via 1,7 m 3G2.5 cable, Ø 8.5 mm, 15 m
Protection class: IP 65
Mass: 12 kg
Accessories: F connector, assembled

ATEX relevant data:

  • Zones: Passive Ex i component for zones 21 and 22, zones 1 and 2
  • Certificate: ISSeP 04ATEX084X
  • Markings: II 2GD Ex ia IIC; IIIC

 

Downloads